NRF-Number :0
Operating voltage : AC 24 V
Power consumption: 2 VA / 2 W
Setpoint setting range : 5…40 °C
Switching differential : Heating: 0.5…6 K Cooling: 0.5…6 K
Communication : Bus: KNX (S-Mode und LTE-Mode mit Synco 700)
Analog inputs, number : 2
Analog outputs : Valve, el. heater: 2 , Fan: 1 (ECM)
Analog outputs, number :3
Analog output, signal : DC 0…10 V
Analog output, current : Max. ±1 mA
Digital inputs, number : 1
Relay outputs : Valve, compressor or el. heater: 2 outputs, 2-position , Fan: 1- or 3-speed
Relay outputs, number : 3
Relay output, switching voltage : AC 24…230 V
Relay output, switching current : 5 (4) A
Type of fixing : Wall mounting with screws
Degree of protection : IP30
Dimensions (W x H x D) : 93 x 128 x 30.8 mm